DG Module: Ready for Harsh Environments.

Liquid-cooled Distributed Generation Power Module

EPC’s liquid-cooled distributed generation modules offer advanced power conversion for today’s distributed generation applications.

Designed with reliability and robustness in mind, the liquid-cooled distributed generation module is a study in simplicity. 

With available power ratings of up to 500kW per module, EPC’s distributed generation modules will take your distributed generation system to the next level.

Key benefits:

  • Compatible with all battery chemistries
  • Multimode operation for grid-tie and off-grid plus parallel UPS backup
  • Storage & Microgrid PCS
  • Liquid cooled for harsh environments
  • Flicker-free resynchronization and reconnection of critical loads after grid outages
  • Real and reactive power control
  • Fully bi-directional

Specs at a Glance

DG Icon5

500kW 

BiDirectional Energy Storage & Microgrid PCS

  • 500kW
  • 30 kg module
  • THD <2%
  • Peak efficiency >98%
  • 50 & 60 Hz operation
  • 3-phase and split-phase modules
  • 600 KVA overload capacity

Liquid Cooled • AC-DC • DC-AC

 
Electrical Specifications
DG LC12/3-5 DG LC12/3-7
480 VRMS | 850 VDC 600 VRMS | 1250 VDC
Frequency range 50 - 60 Hz (field settable)
AC voltage range 208 to 480 VRMS 208 to 600 VRMS
Continuous output power @ 480 VRMS +/- 500 kVA +/- 375 kVA
Peak output power (VA, e.g. motor starts) +/- 600 kVA +/- 450 kVA
AC port configuration 3-wire or split phase
Control modes Voltage command (island), PQ, current command, UPS mode
Current harmonics IEEE 1547 compliant, <2% TDD
Continuous AC Current +/- 600 ARMS +/- 450 ARMS
DC voltage range Up to 850 VDC Up to 1250 VDC
Peak DC to AC efficiency 98.8% 98.4%
Environmental Specifications
Ambient temperature (operation) -20°C to +40°C
Ambient temperature (storage) -20°C to +40°C
Humidity 96% maximum (non-condensing)
Max elevation 2,000m [6,500 ft]
Airborne noise <70 dBA @ 1m
Cooling Liquid
Permissible coolant 25-50% EGW or PGW | corrosion inhibitors per ASTM D6210
Coolant temperature range -20°C to +60°C (de-rating applies above +40°C)
Temperature de-rating 1% /°C from +40°C to +60°C coolant inlet
General Specifications
Maximum dimensions (H x W x D) 511mm x 168mm x 445mm [20.1” x 6.6” x 17.5”]
Weight excluding filters 30 kg [65 lb]
Mounting Wall or floor mount | all orientations permissible
Control interface CAN or Modbus RS485
Required control power 24VDC [18V-27V range], 25W
Black start capable Yes (24V external source required)
Safety features overvoltage, overcurrent, & thermal trips, adjustable IEEE 1547 trip points
Standards compliance UL 1741
Warranty 2 year standard | 5 and 10 year available